Loading...
HomeMy WebLinkAbout12-20-2018 Board of AppealsCITY OFIOWA CITY NOTICE OF PUBLIC MEETING The Iowa City Board of Appeals will convene at 4:00 p.m. on Thursday December 20, 2018 in the Helling Conference Room, 410 Washington St., Iowa City, Iowa TENTATIVE AGENDA 1. Meeting to be called to order 2. Elect Officers for 2018 (Chair and Vice Chair) 3. Discussion and possible recommendation to Council regarding the adoption of the 2018 International Building and Fire Codes. 4. Adjournment CITY OF IOWA CITY Date: December 14, 2018 MEMORANDUM To: Iowa City Board of Appeals From: Tim Hennes, Senior Building Inspector Re: Notable Changes Contained in the 2018 Edition of Building Codes. Following are significant changes made by local amendments and notable changes between the 2015 codes and the 2018 codes. Building Codes The majority of amendments to the building codes are for clarification of a code requirement, to reflect local practices that have evolved from previous building codes and their amendments and to remain consistent with the Fire Code as amended. Following are notable changes or proposed new amendments: Table R301.2(1): Modification to include Manual J criteria on design tables. Comment: Additional information is included on the table to aid the HVAC contractors in designing and sizing the mechanical equipment based on climatic and geographic design criteria based on local conditions. Section R302.5.1: Delete the requirement that requires house to garage doors to have self -closing devices. Comment: The amendment to delete the requirement maintains current requirements. The amendment does not prohibit someone from installing such device. Section R302.13: Delete the requirement to protect the underside of floor/ceiling assemblies in unfinished basements. Comment: This amendment eliminates the requirement to drywall the ceiling or sprinkle an unfinished basement ceiling. The amendment to delete the requirement maintains current requirements. The amendment does not prohibit someone from installing such protection. Section R312.2 (IRC) & 1015.8 (IBC): Delete the requirement to install guards on operable windows that are located less than 24" above the floor and more than 72" above the finish surface on the exterior of the building. Comment: The amendment eliminates the requirement to install guards on all operable windows that meet specified location criteria. The requirement is not consistent with other guard location criteria requirements and could conflict with emergency and escape window opening requirements. The amendment to delete the requirement maintains current requirements. This amendment does not prohibit the installation of fall protection devices on windows. Section R313: Delete the requirement to install a fire sprinkling system in one- and two-family dwelling and townhouses. Comment: This amendment eliminates the requirement for structures regulated by the IRC have an automatic fire suppression system installed. The amendment to delete the requirement maintains current requirements. The amendment does not prohibit the installation of a automatic fire suppression system. Section R314: Delete the requirement to interconnect smoke alarms when a home is being altered, repaired or an addition is added. Comment: This amendment eliminates the requirement for smoke alarms to be interconnected when a home is being altered, repaired or an addition is added. Previous codes have not required this extensive of an update and eliminating the requirement does not forgive the requirement to install battery operated smoke alarms when alterations, repairs or additions. The amendment to delete the requirement maintains current requirements. The amendment does not prohibit someone from installing such protection. Section R320.2: Maintain eight provisions to implement universal design features that provide accessibility, usability and visit -ability for all. Comment: The amendment applies only to new dwelling units and is not required for existing structures for repairs, alterations, change of occupancy or additions unless the square footage of the addition is more than 25% of the existing structure, then, the addition must comply. The minimum usability requirements are as follows: 1. Step -less Entrance: At least one entrance must be designed to provide a step -less entry. 2. Interior doors: At least one bedroom and one bathroom, if either are provided, and all other passage doorway header widths, on the level served by the designed step -less entrance, must be framed to accommodate a minimum 38" clear rough opening. The framing for the doorway width opening may be reduced to accommodate any door size. 3. Sanitation facilities: There must be at least one bathroom containing a water closet (toilet) and lavatory (sink) on the level of the dwelling to be accessed by the designed step -less entrance. The room shall have a minimum thirty inches (30") by forty-eight inches (48") clear floor space at the water closet and lavatory. 4. Wall Reinforcement: A bathroom must be provided with wood blocking installed within wall framing to support grab bars as needed. 5. Decks: All exterior decks and patios surfaces adjacent to the level served by the designed step -less entrance must be built within four inches (4") of the dwelling units finish floor level. 6. Switch and outlet requirements: All wall switches, controlling light fixtures, ans, a temperature control devices and all recepptacles shall be located in an area between fifteen (15) and forty-eight (48) inches above finished floor. 7. Electrical Panel requirements:: Electrical panels on the level of the dwelling o e accesse ye designed step -less entrance shall be located so that the individual circuit breakers are located between 15" and 54 " above the floor. 8. Gara-ges: Must be wired for power operated overhead doors. Section R326: Delete Section R326 Swimming Pools, Spas and Hot Tubs. Comment: This section was moved to the body of the code from the appendix in the previous code cycle. Deleting it results in no change of enforcement for pools, spas and hot tubs. They are still regulated by the electrical and zoning code. Section G2415.3: Eliminates the requirement prohibiting gas piping not extend through any townhouse unit other than the unit served by such gas piping. Comment: Amendment is consistent with the mechanical and fuel gas code with regard to gas piping being installed through dwelling units. Zero lot -line units will still be required to have separate services but single structures that contain multiple units will be allowed to have the gas piping extend through other units. This is consistent with how gas pipe is installed now and in the past. Appendix J (IRC): Existing Buildings and Structures: (1 & 2 family residential) Comment: The purpose of these provisions is to encourage the continued use or reuse of legally existing buildings and structures. These provisions are intended to permit work in existing buildings that is consistent with the purpose of this code. Existing Building Code (multifamily and commercial) Section 102.6 in the International Building Code directs us to the International Existing Building Code (IEBC) for existing structures. Comment: The IEBC allows and encourages the use and reuse of existing buildings while requiring reasonable upgrades and improvements for alterations, repairs, additions, occupancy change, historic and relocated buildings. Energy Code Adopt by reference the State Energy Code: Comment: The State of Iowa adopted the 2012 International Energy Conservation Code (IECC). Referencing the state energy code provides consistency for designers and builders. Tentative schedule for the state to adopt the 2018 IECC is mid 2019. Accessibility Code Adopted by reference the State Accessibility Code: Comment: The State of Iowa Accessibility Code is based on the 2010 ADA Standards for Accessible Design and requirements of the federal Fair Housing Act. Adopting the state accessibility codes by reference provides consistency for designers and builders. Plumbing Code Adopt by reference the State Plumbing Code: Comment: Iowa Code Section 105.4 requires local jurisdictions to adopt the State Plumbing Code. The Iowa State Health Department, as administered by the Plumbing and Mechanical Systems Board, by law adopts the current edition of the Uniform Plumbing Code (UPC) within six months of publication with a few amendments. Tentative schedule for the state to adopt the 2018 UPC is 1st quarter of 2019. Section 422.2.1 of the UPC: Amend to require single use restroom signage. Comment: This amendment will require single user restroom to have signage indicating usage by either sex. Mechanical Code Adopt by reference the State Mechanical Code: Comment: Iowa Code Section 105.4 requires local jurisdictions to adopt the State Mechanical Code. The Iowa State Department of Public Health, as administered by the Plumbing and Mechanical Systems Board, adopts the current edition of the International Mechanical Code within six months of publication with a few amendments. Tentative schedule for the state to adopt the 2018 UPC is 1st quarter of 2019. cc: Tracy Hightshoe, Director, Neighborhood and Development Services Danielle Sitzman, Coordinator, Development Services Prepared by: Tim Hennes, Sr. Building Inspector, 410 E. Washington St., Iowa City, IA 52240; 319-356-5122 ORDINANCE NO. 18- AN ORDINANCE AMENDING TITLE 17, CHAPTER 1, BUILDING CODE, BY ADOPTING THE INTERNATIONAL BUILDING CODE, 2018 EDITION, INCLUDING APPENDIX K, AND THE INTERNATIONAL RESIDENTIAL CODE, 2018 EDITION, INCLUDING APPENDIX F AND APPENDIX J, AND PROVIDING FOR CERTAIN AMENDMENTS THEREOF; ADOPTING SECTION 103.6(1)(A) OF THE CODE OF IOWA (THE STATE ELECTRICAL CODE) AND SECTION 105.4(1)(A) OF THE CODE OF IOWA (THE STATE PLUMBING AND MECHANICAL CODES); REPEALING CHAPTERS 2, PLUMBING CODE, 3, ELECTRICAL CODE, 4, MECHANICAL CODE, 5, ABATEMENT OF DANGEROUS BUILDINGS CODE, AND 13, FUEL GAS CODE; AMENDING CHAPTER 12, ENTITLED APPEALS; AND AMENDING TITLE 6, ENTITLED PUBLIC HEALTH AND SAFETY, CHAPTER 1, ENTITLED NUISANCES; TO PROVIDE FOR THE PROTECTION OF THE HEALTH, WELFARE AND SAFETY OF THE RESIDENTS OF IOWA CITY, IOWA. WHEREAS, the current building code is the 2015 editiontf the international Building Code (IBC) and the International Residential Code (IRC), and the City should adopt the 2018od'itions of those codes; WHEREAS, for purposes of uniformity throughout the State, the State Code has been amended to require all local jurisdictions to adopt the State Plumbing and Mechanical Codes by December 31, 2016; WHEREAS, the fuel gas code is contained in thettate Plumbing Code; WHEREAS, for uniformity in greater Johnson County area, the City should adopt the State Electrical Code; WHEREAS, for more than ten years the City has enforced dangerous buildings through its nuisance code rather than Section 17-5 (Abatement of Dangerous Building Code) because utilizing the judicial system, rather than administrative process, is a better forum both -for the City, as well as the budding owner; and . WHEREAS, the purpose of this ordinance to provide for the protection of the health, welfare and safety of the residents of Iowa City, Iowa. , BE IT ORDAINED BY THE CITY COUNCILOr THE CITY OF IOWA CITY, IOWA: SECTION 1. 1.Sections 17-1, 17-2,17-3 and 17-4 of the Iowa City Code ar%hereby repealed and the following new Sections 17-1, 17-2, 17-3 and 17-4 are enacted In keu thereof. , 17-1-1: Codes Adopted: Subject to the following'amendments, the 2018 edition of the international building code (IBC) including Appendix K, electrical administrative propose, and 2018 edition of the International residential code (IRC) Including Appendrz F, radon control methods, Appendix J, Existing Buildings And Structures, are adopted. Additionally, the City further adopts, Section 103.6(1xa) of the Iowa Code (the Iowa State Electrical Code), Section 105.4(1xa) of the Iowa Code (the Iowa State Mechanical Code), and Section 105.4(1)(a) of the Iowa Code (the Iowa State Plumbing Code). Collectively, they shall be known as the Iowa City building code or the building code. Interpretations of the building official may be guided by publications of the International Code Council, Inc., or the International Existing Building Code. 'r 17-1-2: Interpretation of Building Code provisions: The provisions of this Code shall be held to be the minimum requirements adopted for the protection of the health, safety and welfare of the residents of Iowa City. Any higher standards in the state statute or City ordinance shall be applicable. 17-1-3: Amendments to Code: The following sections of the 2018 edition of the international building code and 2018 edition of the international residential code are amended as follows: Section 101.1 of both the IBC and IRC. Delete Section 101.1 of both the IBC and IRC and insert in lieu thereof the following: 101.1 Title. These regulations shall be known as the Building Code of Iowa City, hereinafter referred to as "this code." Section 105.2 of both the IBC and IRC. Delete Section 105.2 of both the IBC and IRC and insert in lieu thereof the following: 105.2 Work Exempt from Permit. A permit shall not be required for the following: Building 1. One-story detached accessory structures used as tool and storage sheds, playhouses and similar uses, provided the floor area does not exceed 144 square feet provided the structure is not located in aflood hazard area. 2. Fences not over 6 feet (1829 mm) high. 3. Oil derricks 4. Retaining walls which are not over 4 feet (1219 mm) in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge or impounding Class I, II or III -A liquids. 5. Water tanks supported directly on grade if the capacity does not exceed 5,000 gallons (18 925 L) and the ratio of height to diameter or width does not exceed 2 to 1. 6. Sidewalks and driveways not more than 30 inches (762 mm) above grade and not over any basement or story below and which are not part of an accessible route. 7. Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work. 8. Temporary motion picture, television and theater stage sets and scenery. 9. Prefabricated swimming pools which are less than 24 inches deep, do not exceed 5,000 gallons and are installed entirely above ground. 10. Shade cloth structures constructed for nursery or agricultural purposes and not including service systems. 11. Swings and other playground equipment ly 12. Window awnings supported by an exterior wall which do not project more than 54 inches (1372 mm) from the exterior wall and do not require additional sepport. 13. Movable cases, counters and partitions not over 5 feet 1; (1753 mm) in height. 14. For structures regulated by the IRC the reapplicc ion of shingles and roof sheathing provided: a. Less than 50% of the structural sheathing is replaced And othershuctural alterations are not required. b. The structure is not in a Historic Preservation' Overlay Zone or is tiot an Iowa City Historic Landmark. Note: Applying solid sheathing over space sheathing is not considered *uctural sheathing. 15. For structures regulated by the IRC reapplication of siding provided: The structure is not in a Historic Preservation Overlay Zone, or a Conservation . DistrictOverlay Zone, or is m# an Iowa City Historic Landmark. . 16. For structures regulated by the IRC replacing windows provided: a. Replacement window(s) is in` nce with Appendix J. b. The structure is not in a Histor a i'r` tion Overlay Zone, or a Conservation DistrictOverlay Zone, or is not an Iowa City Historic Landmark, 17, For structures regulated by the IRC replacing exterior doors; including garage doors, provided: a. Replacement door(s) is in compliance with Appendix b. They are not street facing .,doors in'shuclurelocatedinaHistoric Preservation Overlay Zone or are not an Iowa City Historic Uthdimark. Note: screen and Storm doors do not require a permit regardless of the location. e: ectricai: 1. P,oitatlq� motors or other portable appliances piiargized by means of a cord or cable having an attAidini nt plug mid to be connected to an approvedreceptacle when that cord or cable is permitted by this code. 2 `Repair or replacement of fixed motors, transformers or fixed approved appliances of the same type and r6tmg in the same location. 3. Tempolary, decorative lightrig. 4. Repair or replacement of current -carrying parts of any switch, contactor, control device or contact device of the same type and/or rating. 5. Replacemenfl pf non -emergency over -current device of the required ampacity and interrupt rating in the same location. 6. Repair or replacement` of Electrodes or transformers of the same size and capacity for signs or gas tube systems. 7. Temporary wiring for experimental purposes in suitable experimental laboratories. B. The wiring for temporary theater, motion picture or television stage sets. Gas: 1. Portable heating, cooking or clothes drying appliances. 2. Replacement of any minor part that does not alter approval of equipment or make such equipment unsafe. 3. Portable -fuel -cell appliances that are not connected to a fixed piping system and are not interconnected to a power grid. Mechanical: 1. Portable heating appliances. 2. Portable ventilation appliances. 3. Portable cooling units. 4. Steam, hot- or chilled -water piping within any heating or cooling equipment regulated by this code. 5. Replacement of any minor part that does not alter approval of equipment or make such equipment unsafe. 6. Portable evaporative coolers. 7. Self-contained refrigeration systems containing 10 pounds (4.54 kg) or less of refrigerant or that are actuated by motors of 1 horsepower (746 W) or less. 8. Portable -fuel -cell appliances that are not connected to a fixed piping system and are not interconnected to a power grid. 9. The replacement of fixed appliances provided however that the replacement appliance is in the same location and has a rating equal to or less than the appliance being replaced, and it is not necessary to remove, replace, alter, or install any additional ductwork or piping. Plumbing: 1. The stopping of leaks in drains, water, soil, waste or vent pipe; provided, however, that if any concealed trap, drainpipe, water, soil, waste or vent pipe becomes defective and it becomes necessary to remove and replace the same with new material, such work shall be considered as new work and a permit shall be obtained and inspection made as provided in this code. 2. The clearing of stoppages or the repairing of leaks in pipes; valves or fixtures, and the removal and reinstallation of water closets, provided such repairs do riot involve or require the replacement or rearrangement of valves, pipes or fixtures. 3. The replacement or removal and reinstallation of anylbdure or appliance, provided, however, that the fixture or appliance is installed at the same location and it is Trot necessary to remove, replace, alter, or install any piping. Exemption from the permit requirements of this Code shall not be deemed to grant authorization for any work to be done in violat6n of the provisions of the Code or any other laws or ordinances of this jurisdiction. Exemption from the permit requirements of this Code shall not be deemed to grant authorization for any work to be done in a manner In violation of the provisions of this Code or any other laws or ordinances of this jurisdiction. Section 105.5 of both the IBC and IRC. Modify Se0on 105.5 of both the IBC and IRC by adding a sentence to the end as follows: In no case shall the permit be effective unless the work covered by the permit has a documented inspection every 6 months ma`mmum and .is completed withjrf 24 months of the date on which the original permit was issued. Section 105.8 of the IBC go R105.10 of the IRd Add two new Sections 105.8 and 105.8.1 to the IBC and R105.10 and R105.10.1 to the IRC As fotidws: 105.8(IBC) R105.10(IRC) beimokionpemgts required. A demolition permit shall be required as follows: 1"For the removal of any buMng or stricture 2 For the removal of any portion of a buildhV (i.e. porch, porch railing, decorative brackets and trim, dpnners, chimneys, *c)that Is located within a Historic Preservation Overlay Zone or a Conservation District Overlay Zone, or is an IowaCfty Historic Landmark. 105.8.1(IBC) and R105.10.1 Requirements. The applicant for any demolition permit shall state on the application the proposed disposal plans for all demolition materials. No demolition permit shall be issued until seven (7)" working days after the date an application has been properly filed and said demolition permit shall not be effective until applicant has posted the premises to be demolished with a notice to be provided by the Clty and as directed by the City; provided, however, that accessory buildings as defined in the Iowa City Zonmb Ordinance and and dangerous buildings shall be exempt from said notice and waiting requirement. Section 105.9 of the IBC and R105.11 of the IRC. Add two new Sections 105.9 to the IBC and R105.11 to the IRC as follows: 105.9 (IBC) and R105.11 (IRC) Pennittee: 1. An electrical, plumbing or mechanical permit may be issued to any person holding a valid master license forthe respective trade as described in Section 17-11-1 E of the Iowa City Code, or to any company who employs a duly licensed master in the respective trade on a full-time basis who supervises the work of the apprentice and or journeymen during the company's normal business hours. 2. An electrical, plumbing or mechanical permit may be issued to the owner of an existing owner - occupied single-family dwelling, pursuant to a valid certificate of occupancy and used exclusively for residential purposes, to do any electrical work in connection with said dwelling and accessory buildings. The owner must personally purchase all material and perform all labor in connection with the permit. Applicants for a homeowner's electrical permit shall pass the designated exam before permit may be issued. 3. The homeowner's test required in subsection 2 of this section may be waived if the applicant is a duly licensed electrician with a minimum of a journeyman status. Section 105.10 of the IBC and R105.12 of the IRC. Add two new Sections 105.10 to the IBC and R105.12 to the IRC as follows: 105.10 (IBC) and R105.12 (IRC) Insurance: Before any permit to perform electrical or plumbing work may be issued, the applicant shall have on file with the building official a copy of a certificate of insurance stating the liability amounts of no less than three hundred thousand dollars ($300,000.00) property damage and five hundred thousand dollars ($500,000.00) bodily injury. The city shall be named as additional insured. The policy shall also provide for at least ten (10) days' notice by the insurer to the city of termination of the policy by the insured or insurer. Electrical permits issued under sections 105.9 (IBC) and R105.11 (ICR) 2 and 3 shall be exempted from this insurance requirement. Section R107.3 of the IRC and Section 108.3 of the IBC. Amend Section R107.3 of the IRC and Section 108.3 of the IBC as follows: R107.3 (IRC) 108.3 (IBC) Temporary Power: Replace the "NFPA 70" with "Iowa State Electrical Code.". Section R108.2 of the IRC and Section 109.2 of the IBC. Delete Section R108.2 of the IRC and Section 109.2 of the IBC and insert in lieu thereof the following: R108.2 (IRC) 109.2 (IBC) Permit Fees and Valuations. The fee for any permit shall be as set forth in the permit fee schedule as established by resolution of the City Council The determination of value or valuation under any of the provisions of this Code shall be made by the Building Official. The value to be used in computing the building permit and building plan review fees shall be the total value of all construction work for which the permit is issued, as well as all hoM work, painting, roofing, site grading, paving, landscaping, elevators, and other permanent equipment. The velue to be used in computing the value of construction for reports shall be the total value of all constru0on work for which the permit is issued, as well as all finish work, painting, roofing, electrical, plumbing, heating, air conditioning, site grading, paving, landscaping, elevators, fire extinguisher systems and ogler permanent equipment. Section R108.3 of the IRC and Section 109.3 of the IBC Delete Sec0on R108.3 of the IRC and Section 109.3 of the IBC and insert in lieu thereof the following: R108.3 (IRC) 10,4 � (IBC) Pion Review Fees. When a plan or other data are required to be submitted by Section 106 and the value of the proposed building or work exceeds fifteen thousand dollars ($15,000), a plan review fpe Shall be paid before the permit may be issued. Should the project be abandoned and the permit not issued after,the plan review has been started, the plan review fee shall still be due and payable. The plan review'fee shall be as set forth by resolution of City Council. Plan review fees are separate fees from the permit -fee specified, in Section R108.2 and 109.2 and are in addition to permit fees. Section R108. 5 of the IRC and Sectb 1�09.6 of the IBC: Delete Section R108.5 in the IRC and Section 109.6 of the IBC and insert The thereof Hiefo(lowing: R108.5 (IRC) 109.6 IBC Refunds: The Building Official may authorize the refunding of any fee paid hereunderwhich was erroneously paid or collected. The Building Official shall not authorize the refunding of any fee paid except upon written application filed by the original permittee within one hundred eighty (180) days from the date of fee payment. Section R108.6 of the IRC and Section 109.4 of the IBC. Delete Section 108.6 of the IRC and Section 109.4 of the IBC and insert in lieu thereof the following: R108.6 (IRC) 109.4 (IBC) Work commencing before permit issuance: Any person who commences work on a building, structure, electrical, gas, mechanical or plumbing system before obtaining the necessary permits shall be subject to a fee equal to the amount of the permit fee if a permit were issued. This fee shall be collected whether or not a permit is issued. The payment of such fee shall not exempt any person from compliance with all other provisions of this Code or from any penalty prescribed by law. Only the Building Official may reduce this fee when it is demonstrated that an emergency existed that required the work to be done without a permit. Section R112 of the IRC and Section 113 of the IBC. Delete Section K1 1l of the IRC and Section 113 of the IBC and insert in lieu thereof the following: Section R112 of the IRC and Section 113 of the IBC Appeals: See Title 17 Chapter 12 Appeals in the City Code. Section 202 of both the IBC and IRC. Add new definition as follows: Authority Having Jurisdiction. The organization, office, or Individual responsible for approving equipment, materials, an installation, or a procedure. Section 202 of both the IBC and IRC. Add new definition as follows: Chief Electrical Inspector. A building inspector who either is the authority having jurisdiction or is designated by the authority having jurisdiction and is responsible for administering the requirements of this code. Section 202 of both the IBC and IRC. Add new definition as follows: Electrical Inspector. A building inspector authorized to perform electrical inspections. Section 202 of both the IBC and IRC. Add new definition as follows: Family: See Title 14 Chapter 9 Article A Zoning Definitions in the City Code. Section 202 of both the IBC and IRC. Add new definition as follows: Emergency Communications Center. Shall mean the the Johnson County Emergency Communications Center. Section 202 of the IBC and IRC. Modify definitions as foltdws; Habitable space: Add a sentence to the end of the, definition of habitable space or room to read as follows: Basement areas finished to a degree to encourage their use as anything other than storage or mechanical rooms shall be considered habitable space. Section R202 of the IRC. Delete definition of Accessory,�tructure and insert in lieu thereof the following: ACCESSORY STRUCTURE. See Title 14 Chapter 9 Article A Zoning Definitions in the City Code. Table R301.2 (1) of the IRC Modify by inserting data iri the table as follows: Ground wend Deign SeW SYbiedtobamage From Wlgox Ira Iood Haeards MrFreedoi, Mee" Topcepephlceffems, Snow Dal(n Frert ' Des". Bernier Imd Speed SWchl wind region, or m*o, Ilne Temp Underlay FIRM Index Annul Temp Wepthedng Torn" Inert NFIP (mph) Required Maps Windbume debdp - f depth Bona .. Modem 25 115 No A &wdre 42" m ' S°F Yes 5/22/77 2/15/07 moo 50-F Heavy MANUA 3 DESIGN CRITERIA Elevadon Lailtatb ViRew Somerm CooDeg - AMtode Correetim Iotloor Dedgo Design Temperature Eativg Temperature Factor Tempmatpre Coding Dife. 661' 41° .6° 89° N/A 72° 75° 79° Coormg Wi"d Vrbdq Wind,l•gla Coincident Wet Dely Range Wiafaamnidity 8ummm FW.Wlty Tempmature Deddeg CLWpg._ Be% Diffmrnce 14° 25° ra. 76° M 39 gr/Ib dill. 53 gulb dill. Section R302.5.1 of the IRC. Delete Section R302.5.1 of the IRC and insert in lieu thereof the following: R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 1 3/8 inches (35 mm) in thickness, solid or honeycomboore steel doors not less than 1 3/8 inches (35 mm) thick, or 20-minute fire -rated doors. Section R302.13 of the IRC. Delete Section R302.13 of the IRC entirely. Section R310.6 of the IRC. Delete Section R310.6 in the IRC and insert in lieu thereof the following: R310.6 Alterations or repairs of basements in structures built after May 10, 1989. An emergency escape and rescue opening is not required where existing basements undergo alterations or repairs. Alterations or repairs in structures built prior to May 10, 1989 shall conform to Appendix J Section AJ102.4 Replacement windows. Exception: New sleeping rooms created in an existing basement shall be provided with emergency escape and rescue openings in accordance with Section R310.1. Section R312.2 of the IRC and 1015.8 of the IBC. Delete Section R312.2 of the IRC and 1015.8 of the IBC entirely. Section R313 of the IRC: Delete Section R313 of the IRC entirely. Section R314.4 of the IRC. Amend Section R314.4 in the IRC by adding an exception as touows: Exception: Interconnection of smoke alarms in existing areas shall not be required where alterations or repairs do not result in removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available that could provide access for interconnection with removal the interior finish. Section R320.2 of the IRC. Add Section R320.2 in the IRC as follows: R320.2 Accessibility for projects other than those mentioned in Section R320.1. R 320.2.1 Scope. The provisions of this section are enacted to implement universal design features that provide accessibility, usability and visit -ability for all. R320.2.2 Definition. Public funds shall mean funding of assistance from the City of Iowa City or any agent thereof through any of the following means: 1. a building contract or similar contractual agreement involving a City -funded program or fund; 2. any real estate received by the owner through a subsidy, lease, or donation by the City or its agents; 3. preferential tax treatment, bond assistance, mortgage assistance, or similar financial advantages from the City or its agents; 4. disbursement of federal or state construction funds Including a Community Development Block Grant; or 5. a City contract to provide funding or a financial benefit for housing. R320.2.3 Applicability. The amendment applies to, new one- and two-family dwellings and is not required for new townhouses, accessory apartments or existing structures for repair's alterations, change of occupancy or additions unless the square footage of the addition is more than 25% of The existing structure, then, the addition must comply. Exception: Applies to new townhouses constructed using public funds The minimum usability requirements are as follows 1. Step -less Entrance: At least one building entrance must be designed, without encroaching into any required parking space, that complies with Abe Iowa City Building Code standard for an accessible entrance on an accessible route served by a ?amp in accordance with section R311.8 or a no -step entrance. The accessible route must extend from a vehicular drop-off, or parking to a building entrance. The entry door must have a minimum net clear opening of thirty4 Wo inches (321)' Exception: 1. If public funds are used the step -less entrance must be provided. 2. The building official may waive this regt"ment based upon the determination that strict compliance is financially or environmentally impractical. Split-level and townhouse style homes may be exempted. Note: Iowa City code only requires one parking space for single family dwellings. 2. Interior doors: At least one bedroom and one bathroom (if either are provided) and all other passage doorway headerwidths, on the level served by the designed step -less entrance, must be framed to accommodate a minimum 38" clear rough opening. The framing for the doorway width opening may be reduced to accommodate any door size Exception: 1.If public funds are used the minimum door clear opening shall be thirty-two inches (32") when the door is open ninety degrees (90 ), measured between the face of the door and the opposite stop. 2.Doors serving closets twenty-four inches (24") or less in depth need not be framed to 38" clear opening width. Note: A 34" door hung in the standard manner provides an acceptable 32" opening. 3. Sanitation facilities: There must be at least one bathroom containing a water closet (toilet) and lavatory (sink) on the level of the dwelling to be accessed by the designed step -less entrance. The room shall have a minimum thirty inches (30") by forty-eight inches (48") clear floor space at the water closet and lavatory. The clear floor space can be shared by both fixtures. The clear floor space shall not be obstructed by a doorway swing. The plans must show a shower, bathtub or combination tub/shower can be provided within the room or an adjoining room without removing part of the concrete floor to provide necessary plumbing to the future plumbing fixture(s). Exception: 1.If public funds are used a shower, bathtub or combination tub/shower shall be provided within the room. 2.Doors may swing into the clearfloor space provided at any fixture if sufficient maneuvering space is provided within the room for a person using a wheelchair or other mobility aid to enter and close the door, use the fixtures, reopen the door and exit. Maneuvering space may include any knee space or toe space available below bathroom fixtures. 3.The building official may waive this requirement based on the determination that strict compliance is financially impractical. 4. Wall Reinforcement: A bathroom must be provided with wood blocking installed within wall framing to support grab bars as needed. The wood blocking, when measured to the center, will be located between thirty-three inches (33") and thirty-six inches (36") above the finished floor. The wood blocking must be located in all walls adjacent to and behind a toilet. Exception: Backing is not required behind pre -manufactured showers and bathtubs. 5. Decks: All exterior decks and patios surfaces adjacent to the level served by the designed step -less entrance must be built within four inches (4") of the dwellings finish floor level. Decks shall be a minimum 50% the size of a patio that is served by level served by the designed step -less entrance. 6. Switch and outlet requirements: All wall switches, controlling light fixtures, fans, all temperature control devices and all receptacles shall be located in an area between fifteen (15) and forty-eight (48) inches above finished floor. The height will be determined by measunpg from the finished floor to the center of the device. When the control or receptacle placement, is prohibited ,by the height of the window or design feature, alternative locations may be approved by the'bullding official 7. Electrical panel requirements: Electrical panels on the level of the dwelling to be accessed by the designed step -less entrance shall be located so that the individual circuit breakers are located between 15" and 54 " above the floor. 8. Garaaes: Must be wired for power operated overhead Section R322 of the IRC. Delete section R322 of the IRC and invert in lieu thereof the following: R322. See Title 14 Chapter 5J Flood Plain Management Standards in the City Code. R322.1 Flood Resistive Materials. Buiki(ng materials and installation methods used for flooring and interior and exterior walls and wall coverings below the elevatuQn required in Title 14 Chapter 5J Flood Plain Management Standards in the City Code shall be flood damage-resl4tant materials that conform to the provisions of FEMA TB-2. Section R326 of the IRC. Delete Section R326 of the M,entirely. Section R403.1.4.1 of the IRC Modify by deleting all exceptions and inserting in lieu thereof the following: Exceptlons 1.One story detached accessory buildings of wood orsteel frame construction not used for human occupancy and not exceedingone thousand (1,000) square feet m floor area may be constructed using slab on grade construction as follows The slab shall be three. and one half inches thick, poured monolithically with thickened perimeter footings extending twelve inches (12") below finish grade and be twelve inches (12") wide at ,the base. The top of the foundation shall not be less than six inches (6") above finish grade. Reinforcement of the slab, inducting the. thickened portion, shall be minimum 6x6-10/10 welded wire mesh, #4 deformed reinforcing bars at twenty four inches (24") on center each way or fiber mesh reinforced concrete. 2. One-story wood or metal frame building not used for human occupancy and not over 200 square feet in floor area may be constructed with walls supported on a wood foundation plate or "skids" when approved by the building official 3. Decks not supported by the structure need not be provided with footings that extend below the frost line. Section R404.1.1 of the IRC: Amend Section R4041.1 of the IRC by addino an Exception after number 2 as follows: Exception: Foundation walls with unbalanced lateral forces created by finish grade, i.e. walkout basements which are exempt from the Iowa Architectural Ad shall be designed by a licensed structural engineer or constructed in accordance with the Table R404.1.1(5) and diagram as follows: Table M01.1.10) ®•Cmneraess 6.6panAWtll Txnkl neu a.FOlbel T L= O1- e'&f1'FuulPlellon welt � 1 rtoAdersromahh hmh aundaaion mllMwell21 am W wellThPaeu is,Powle Parbmal Canerlsa ID'orkx r M ®31' 3'-D' w ta1Y r 45@ 1Ya14' 3'. 76On. 3'-D" Wow 1Y 011' Y-6- I6'a18' Ir ais 14' g-C 1611010' W d601Y 3'-D" Froawa6&F NIwe&.wt) assess ' L Camrbrsomreeubedlnaddrdmaha nWreldortlo& 1. AII[omm&rrelnaNigaplku ahelibe based embamuen on4'. 3. aspm(S)lsmslathan 16, Ihemhlhnumdwraknal)D) shell beg. Section R404.1.3 of the IRC Modify Section R404.1 3-by adding a second paragraph as follows: Wall thickness may be reduced to eight inches (&') if a m)ntmum of three (3) one-half inch diameter deformed ASTM A615 grade 40 steel bars a4 placed horizontally at the center of the wall thickness with one bar located within 14" of the top one bar with(n 14" of the bottom and one bar located within 14" of the mid -height of the wall provided the wall height does, not exceed eight feet (8'). Section 423A of the IBC. Delete Section 423.4 in its entirety and insert in lieu thereof the following: Group E occupancies. In areas where the shelter design wind speed for tornados is 250 MPH in accordance with Figure 304.2(1) of ICC 500, all new Group E occupancies shall have a storm shelter constructed in accordance with ICC 500 The shelter shall be capable of housing the total occupant load of the Group E occupancy df as required by 661-301 of the Iowa State Building Code, whichever is more restrictive. Exceptions: 1. Group E,day care fac4ages. 2. Group E occupancies accessory to places of religious worship. 3. Buildings meeting the requirements for shelter design in ICC 500. 4. Portable buildings Section 502.1 of the IBC tF1. Modify by inserting the following alter the second sentence: From 100-199 feet from the street the number shall be a minimum of 6 inches high with a minimum stroke of 0.5 inches. From 200-299 feet from the street the numbers shall be a minimum 8 inches high with a minimum stroke of 0.5 inches. For each additional 100 feet from the street, the number shall increase by an additional 2 inches in height. Measurements to determine the minimum number size shall be measured from the approved address location to the center line of the street for which the premises is addressed. Section R807.1 of the IRC. Modify by adding a sentence at the end of the second paragraph as follows: The opening shall not be located in a closet, bathroom, mechanical room, laundry room, or similar room or location. Section 903.2.1.2 of the IBC (F). Modify section 903.2.1.2 by adding a second paragraph as follows: Group A-2 Occupancies that existed prior to August 1, 2007: An automatic sprinkler system shall be provided throughout the A-2 occupancy with an occupancy load of 100 or more that have an ABDL and there is a change in business ownership, defined as the sale, transfer, or assignment of any legal or equitable ownership interest, except that the owner may show to the building official's satisfaction that said change in ownership is one of form and not substance. Section 903.2.1.8 of the IBC R. Add a new Section 903.2.1.8 as follows: Section 903.2.1.8. An automatic sprinkler system shall be provided throughout buildings and portions thereof used as new Group B occupancies with an ABDL or existing group B occupancy with a new (not a renewal) ABDL located on a floor other than the level of exit discharge. The automatic sprinkler system shall be provided throughout the floor area where the new Group B occupancy with an ABDL or where the group B occupancy with a new ABDL is located, and in all floors between the Group B occupancy and the level of exit discharge. Section 903.2.2 of the IBC (F). Delete Section 903.2.2 of the IBC and replace with: 903.2.2 Group B ambulatory health care facilities. An automatic sprinkler system shall be installed throughout all fire areas containing a Group B ambulatory healt4 care facility occupancy. Section 903.3.5.3 of the IBC (F). Add a new Section 903 3'5.3 in the IBC 1p read as follows: 903.3.5.3 Water supply safety margin. Provide a'malimum 10%, or 5 psi safety margin (whichever is greater) above static pressure in the fire proteollon system hydraulic calculations. Section 903.4.2 of the IBC (Fl. Delete Section 903.4.2 of the IBC and replace with: ` 903.4.2. Alarms. An approved weatherproof homistrobe, device shall be mounted directly above the fire department connection between seven (7) and tan" (10) feet in height above grade. The water - flow alarm device shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed inthe system. Approved and supervised audible visual notification appliances shall be installed on each level of the interior of the building as required by the fire code official and NFPA 72. _Section 903.6 of the IBC (Fl. Add a new Section 903 6 to the IBC to r"d as follows: 903.6 Zones. Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13 or NFPA 13R and shall provide a sprinkler control valve and water flow device for each normally occupied floor Section 905.1.1 of the IBC (F). Add a riew Section 2M.1.1 to the IBC to read as follows: 905 1 1 Delete all references to Clatios II standpipe systems and replace with Class III standpipe systems Section 905.4 of the IBC (F). Amend Section 905.4 by deleting #1 and replace with: 1. In every required interior exit stairway, a hose connection shall be provided for each story above and below grad plane. Hose connections shall be located at intermediate landings between stories, unless otherwise approved by; the fire pode official. Exception: A single hose connection shall be permitted to be installed in the open corridor or open breezeway between open stairs that are not greater than 75 feet apart. Section 906.1 of the IBC (F). Delete the exceptions 1 and 2 without substitution. Section 906.3 of the IBC (F). Add a sentence to the end of the section to read as follows: The minimum rating of any required portable fire extinguisher for Class A, Class B, or Class C hazard shall be 2-10 B C Section 907.2 of the IBC (F). Delete the section and replace with: 907.2 Where required -new buildings and structures. An approved and addressable manual, automatic, or manual and automatic fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.23 and provide occupant notification in accordance witn 9u7.5, uniess other requirements are provided by another section of this code or fire code official. A minimum of one manual fire alarm box shall be provided in an approved location to initiate a fire alarm signal for fire alarm systems employing automatic fire detectors or water -flow detection devices. Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, a single fire alarm box shall be installed. EXCEPTION: 1. The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service. 2. The manual fire alarm box is required for Group R-2 occupancies to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. The manual fire alarm box shall not be located in an area that is accessible to the public. 3. Multi -tenant buildings required to have a manual/automatic fire alarm system shall install a minimum of one manual pull station per tenant space. Section 907.2.1 of the IBC (F). Delete the "exception" in section 9u7 z 1 in its entirety and insert in lieu thereof the following exceptions: EXCEPTION: 1) Except for Group A-2 occupancies with occupant loads of 200 or more, manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow 2) Group A-2. An automatic/manual fire alarm, system shall be installed in Group A-2 occupancies with and occupant load of 200 or more. Activaition of the fire alarm shall additionally cause: a. Illumination of the protected premises to not less than 10 foot-candles over the area of the room at a height of 30 inches above the floor, and b. All conflicting or confusing sounds and visual distraction to automatically stop. Section 907.2.3 of the IBC (F). Modify by adding a sentence to the end of the first paragraph as follows: New and existing educational occupancies shall have a monitored fire alarm system. Section 907.2.3 of the IBC (F). Modify by adding a 51n exception as follows 5. Day care occupancies classified as Group E Occupancy shall not require a monitored fire alarm system unless required elsewhere in the code., ' Section 907.2.10.2 of the IBC Modify by adding a fourth location requirement as follows: 4. Supervised smoke alarms shall be installed in all common corridors and at the top and bottom of all stairway enclosures in Groups R-2, R-4 and 1.1 occupancies. In corridors, detectors shall be located within fifteen (15) feet of the end of the corridor and in such a way that one detector is located for each thirly (30) feet of corridor length or spaced as allowed by the code. Section 907.2;,U.2 of the IBC. Delete without substitution. Section 907.4.2 of the IBC. Modify by adding a sentence to the end of the section to read as follows: Where in the opinion of the code official manual fire alarm boxes may be used to cause false fire alarms, the code official is authorized to modify the requirements for manual fire alarm boxes. Section 907.6.4 of the IBC (F) Modify by deleting the exception and inserting in lieu thereof the following exception: Exception: Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13 and shall provide a sprinkler control valve and waterflow device for each normally occupied floor. Section 907.6.4.3 of the IBC (F). Add a section to read as follows: Section 907.6.4.3 Zone and address location labeling. Fire alarm and/or annunciator panels shall have all zones and address points plainly and permanently labeled as to their location on the outside of the panel or on an easily readable map of the building, if no display is present. Section 907.6.6 of the IBC (F). Modify Section 907.6.6 by adding two sentences to the end as follows: Each address point identification, shall have an alpha/numeric descriptor location. Alpha/numeric descriptor locations are required to be reported to the Emergency Communications Center upon activation of supervisory and/or alarm conditions as specified by the fire code official. Section 907.9 of the IBC (F). Add a new Section 907.9 as follows: 907.9 Approved hold open devices. When installed in buildings that have a fire alarm system and /or sprinkler 10 system, all approved hold open devices shall release upon activation of the fire alarm and/or sprinkler water - flow activation. Section 912.4.1 of the IBC (F). Delete Section 912.4.1 and replace with the following: Section 912.4.1 Locking fire department connection caps. Locking fire department connection caps approved by the fire department are required for all new construction that have a water -based fire protection system and existing structures that have a water -based fire protection system shall be required Immediately after conducting the five-year obstruction and maintenance testing, or if one or more of the fire department caps are missing. Section 912.7 of the IBC (F). Add a new section 912.7 to the IBC to read as follows: 912.7 Size. Minimum fire department connection size shall be 2 %2" inch National Standard Thread. Section 912.8 of the IBC (F). Add a new section 912.8 to the IBC to real as follows: 912.8 Water supply. Fire department connections shall be located not more than 100 feet from a hydrant or as approved by the fire code official. Section 1011.3 of the IBC. Modify by adding a third exception as follows: EXCEPTION: 3. Stairs within individual dwelling units Af Residential Group R occupancies that existed prior to 8/28/02 (adoption of the 2000 IRC) are permitted a 78-inch (6'-6") headroom clearance. Section 1015.8 of the IBC. Delete Section 1015.8 of the IBC entirely Section 1023.4 of the IBC. Modify Section'10234 by adding a fourth unnumbered paragraph as follows: Fire door assemblies that provide access to a noh-pressurized interior exit of R-2 occupancies shall also be automatic closing by actuation of a smoke detector Section 1029.2 of the IBC (Ft. Modify by adding a new exception follows., EXCEPTION: 1) The main entrance/exit.of A-2 occupancies shall be of a width that accommodates not less than two-thirds of the total occupant load Section 1030.1 of the IBC. Modify by deleting the exceptions and inserting In lieu thereof the following: EXCEPTIONS. 1 The emergency escape and rescue opening is permitted to open onto a balcony within an atrium in accordance with .the requirements of Section 404 provided the balcony provides access to an exit and the dwelling unit or sleeping room has a means of egress that is not open to the atrium. 2. Regardless of what Tables 100¢ 3.3(1) and 1006.3.3(2) allow, all group R-2 occupancies other than hotels and motels must be provided with emergency escape & rescue openings. 3. Emergency escape and rescue openings are not required from basements or sleeping rooms that have an exit door or exit access door that opens directly into a public way or to a yard, court or exterior exit balcony that opens to a public way. Section 1030.6 of the IBC. Add a new Section 1030.6 to the IBC to read as follows: Section 1030.6. Emergency escape windows under decks and porches. Emergency escape windows are allowed to be installed under decks and porches provided the location of the deck allows the emergency escape window to be fully opened and provides a path not less than 36 Inches in height to a yard or court. Chapter 11 of the IRC. Delete Chapter 11 in its entirety and insert in lieu thereof the following: Chapter 11 Energy Efficiency, Section N1101. Energy efficiency for the design and construction of building regulated by this code shall be as required by 661-303 of the Iowa State Administrative Code. Chapter 11 of the IBC. Delete Chapter 11 in its entirety and insert in lieu thereof the following: Chapter 11 Accessibility, Section 1101. Buildings or portions of buildings shall be accessible to persons with disabilities as required by 661-302 of the Iowa State Administrative Code. Section 1208.2 of the IBC. Modify by adding a second unnumbered paragraph as follows: 11 1208.2 Attic spaces. The opening shall be located in a comoor, hallway, or other readily accessible location. The opening shall not be located in a closet, bathroom, mechanical room, laundry room, or similar room or location. Attics with a maximum vertical height of less than thirty inches need not be provided with access openings. Chapter 13 of the IBC. Delete Chapter 13 in its entirety and insert in lieu thereof the following: Chapter 13 Energy Efficiency, Section 1301. Energy efficiency for the design and construction of building regulated by this code shall be as required by 661-303 of the Iowa State Administrative Code. Section 1402.6 and 1402.7 of the IBC. Delete Sections 1402.6 and 1402.7 of the IBC and insert in lieu thereof the following: Section 1402.6. See Title 14, Chapter 5, Article J Flood Plain Management Standards in the City Code. Section 1612 of the IBC. Delete Section 1612 of the IBC and insert in lieu thereof the following: Section 1612. See Title 14, Chapter 5 Article J Flood Plain Management Standards in the City Code. Section G2406.2 (303.3) of the IRC. Prohibited locations of the IRC. Modify by deleting exceptions 3 and 4. Section G2415.3 (404.3) of the IRC. Prohibited locations of the IRC Modify by deleting the last sentence. Part VII Plumbing, Chapters 25 through 33 inclusive of the IRC. Delete Part VII Plumbing Chapters 25 through 33 inclusive of the IRC and insert the following: Part VII Plumbing, Chapter 25 Section P2501 GENERAL P2501.1 Scope. Plumbing systems shall comply with the Iowa State Plumbing Code. Administrative Provisions. The Plumbing Code shall be administered in accordance with administrative provisions in chapter 1 of this code as amended. Chapter 27 of the IBC. Delete Section 2701`General of the IBC and insert the following: Section 2701 GENEREAL Section 2701.1 Scope Electrical systems shall comply with the Iowa State Electrical Code. Section 2701.2 Administrative Provisions. The Electrical Code shall be administered in accordance with administrative provisions in chapter 1 of this code as amended and Appendix K as amended. Chapter 28 of the IBC. Delete chapter 26 of the IBC and insert the following: Chapter 28 Mechanical Systems Section 2801.1 Scope. Mechanical systems shall comply the Iowa State Mechanical Code with the following amendments:. Administrative Provisions. The Mechanical Code shall be administered in accordance with administrative provisions in chapter 1 of this code as amended. Commercial Kitchen Hood Exhaust Termination In addition to the code requirements for commercial kitchen hood exhaust terminations locations, the following shall apply: For new construction, change in occupancy or change in use, that requires a new commercial kitchen hood or revisions to an existing commercial kitchen hood, the new or existing commercial kitchen hood exhaust duct shall terminate as follows: 1. Above the roof level without passing through an exterior wall; or 2. Through an alley facing exterior wall provided the termination is above the roof level; or 3. To an alley right of way per 3202.3.2 of the International Building Code. Chapter 29 of the IBC. Delete Chapter 29 of the IBC and insert the following Chapter 29 Plumbing Systems Section 2901.1 Scope. Plumbing systems shall comply with the Iowa State Plumbing Code. 12 Administrative Provisions. The Plumbing Code shall be administered in accordance with administrative provisions in chapter 1 of this code as amended. Section 422.2.1 of the UPC. Delete Section 422.2.1 and insert in lieu thereof the following: Section 422.2.1 Single Use Toilet Facilities. Single use toilet facilities and family or assisted use toilet facilities shall be identified with signage indicating use by either sex. Section 3002.4 of the IBC. Delete Section 3002.4 of the IBC and insert in lieu thereof the following: 3002.4 Elevator car to accommodate ambulance stretcher. In buildings four or more stories above, or four or more stories below, grade plane, at least one elevator shall be provided for fire department emergency access to all floors. The elevator car shall be of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches (610 mm by 2134 mm) with not less than 5-inch (127 mm) radius corners, in the horizontal, open position and shall be identified by the international symbol for emergency medical services (star of life). The symbol shall not be less than 3 inches (76 mm) high and shall be placed inside on both sides of the hoistway door frame. Part Vlll Electrical Chapters 34 throuch 43 inclusive of the IRC: Delete Part VIII Electrical Chapters 34 through 43 inclusive of the IRC and insert the following: Part VIII Electrical, Chapter 34 Section E3401 GENERAL E3401.1 Applicability. Electrical systems shall comdlywith the Iowa,State Electrical Code. (Appendix K of the IBC.) Section K103.2 of the IBC. Work exempt from permit.. Delete Section K103.2 in the IBC and insert in lieu thereof the following: Section K103.2 Work exempt from permit. See section 105.2 in both the IRC and IBC Section K106.5 of the IBC. Add a new Section K106. 5 as follows Section K106.5 Energy Connections, An electrical system or equipment regulated by this code for which a permit is required shall not be connected to a source of energy or power until approved by the building official. Section K106.6 of the IBC. Add a new Section K106 6 as follows. Section K106. 6 Temporary Energy Connections The building official may authorize the temporary connection of the electrical system or equipment to the source of energy or power for the purpose of testing the equipment, or for use under aaemporary certificate of occupancy. (Appendix J of the IRC. } Section AJ102 4 of the IRC. Delete Section AJ102.4 of the IRG and insert in lieu thereof the following: AJi1024 Replacementawndows and doors. Regardless of the category of work, where an existing window or door, fnduding the sash and glazed portion, or safety glazing is replaced, the replacement window, door or safety glazing shall comply with the requirements of Sections AJ102.4.1 through AJ102.4.3, as applicable. Section AJ102.4.1 of the IRC. Delete Section AJ102.4.1 of the IRC and insert in lieu thereof the following: AJ102.4.1 Energy efficiency. Replacement windows or doors shall comply with the requirements of Chapter 11. Section AJ102.4.4 of the IRC Delete Section AJ102.4.4 of the IRC entirely. Section AJ501.7 of the IRC. Delete Section AJ501.7 and insert in lieu thereof the following: AJ501.7 Ceiling height. Habitable spaces created in existing basements or attics shall have ceiling heights of not less than 6 feet, 8 inches (2032 mm), except that the ceiling height at obstructions shall be not less than 6 feet 4 inches (1930 mm) from the basement or attic floor. Existing finished ceiling heights in nonhabitable spaces in basements or attics shall not be reduced. Section AJ501.8.1 of the IRC. Delete Section AJ501.8.11 of the IRC and insert in lieu thereof the following: AJ501.8.1 Stair width. Existing basement and attic stairs and handrails not otherwise being altered or modified shall be permitted to maintain their current clear width at, above and below existing handrails. Section AJ501.8.2 of the IRC. Delete Section AJ501.8.2 of the IRC and insert In lieu thereof the following: AJ501.8.2 Stair headroom. Headroom height on existing basement or attic stairs being altered or modified shall not be reduced below the existing stairway or attic finished headroom. Existing basement or attic stairs not otherwise being altered shall be permitted to maintain the current finished headroom. Section AJ501.8.3 of the IRC. Delete Section AJ501.8.3 of the IRC and insert in lieu thereof the following: 13 AJ501.8.3 Stair landing. Landings serving existing basement or attic stairs being altered or modified shall not be reduced below the existing stairway landing depth and width. Existing basement or attic stairs not otherwise being altered shall be permitted to maintain the current landing depth and width. Section AJ601.4 of the IRC. Delete Section AJ601.4 of the IRC and insert in lieu thereof the following: AJ601.4 Ceiling height. Habitable spaces created in existing basements and attics shall have ceiling heights of not less than 6 feet, 8 inches (2032 mm), except that the ceiling height at obstructions shall be not less than 6 feet 4 inches (1930 mm) from the basement or attic floor. Existing finished ceiling heights in nonhabitable spaces in basements or attics shall not be reduced. 17-1-4: Penalties for violations: Violation of this chapter shall be a municipal infraction punishable by a penalty as provided for in subsection 1-4-2D of the City Code. 4. Except as provided herein, any reference to the "Plumbing Code," the "Electrical Code," or the "Mechanical Code" is deleted and replaced with "Building Code." SECTION II. REPEALER. All ordinances and parts of ordinances in pbnfhct with the provision of this Ordinance are hereby repealed. SECTION III. SEVERABILITY. If any section, provision or part of the Ordinance shall be adjudged to be invalid or unconstitutional, such adjudication shall not affect the validity of the Ordinance as a whole or any section, provision or part thereof not adjudged invalid or unconstitutional SECTION IV. EFFECTIVE DATE. This Ordinance shall be in effect after final passage,approval and publication as provided by law. Passed and approved this day of 2015. MAYOR Approved by City Attorneys Office ATTEST. CITY CLERK 14 CITY OF IOWA CITY Date: November 8, 2018 To: Board of Appeals From: Brian Greer, Fire Marshal MEMORANDUM Re: Notable changes to the 2018 edition of the International Fire Code The fire department presents for your review, notable changes to the 2018 International Fire Code (IFC). 104.9 NEW. SECTION. Alternative materials, design and methods of construction and equipment- This allows the fire code official to accept a proposed a material, design, or method of construction if it complies with the intent of the provisions of this code. 105.6.30 NEW SECTION. Mobile food preparation vehicles — Requires a permit for mobile food preparation vehicles equipped with appliances that produce smoke of grease -laden vapors. 202 NEW DEFINITIONS. General Definitions — New definitions to provide a more complete list of general definitions. 315.7 NEW SECTION. Outdoor pallet storage — Provides requirements for the outdoor storage of idle pallets. 319 NEW SECTION. Mobile Food preparation Vehicles — The requirements in this section discuss requirements for exhaust hoods, fire protection, storage, and fuel systems associated with mobile food preparation vehicles. 404.2.3 REVISED SECTION. Lockdown plans — Provides additional guidance on procedures, methods, training, and drills associated with a code compliant lockdown plan. 510 REVISED SECTION. Emergency Responder Radio Coverage — Requirements for emergency responder radio coverage have been revised to address industry and equipment enhancements. 607. NEW EXCEPTIONS. Commercial Kitchen Hoods —New exceptions regarding whether a Type 1 hood is required. Chap. 7 REVISED CHAPTER. Chapter 7- Fire and Smoke Protection Features — A large percentage of this chapter has been added or amended to include more detail related to this topic. 807.4 NEW SECTION. Artificial decorative vegetation — Establishes limitations on where and how much artificial decorative vegetation is allowed. 901.4.6 MODIFIED SECTION. Pump and riser room size — Additional sections provide requirements for access, door markings, environment, and lighting in these rooms. 901.6.2 NEW SECTION. Integrated testing — Establishes requirements for testing where multiple fire protection systems and life safety systems are integrated. 903.2.1 MODIFIED SECTION. Sprinklers in Group A Occupancies — This section clarifies the requirements for fire sprinkler protection in Group A occupancies. 903.2.3 MODIFIED SECTION. Sprinklers in Group E Occupancies — Establishes new threshold for installation of automatic sprinkler system in all Group E fire areas with an occupant load of greater than 300 persons. 903.3.1.2.3 NEW SECTION. Protection of Attics in Group R Occupancies — Sprinkler protection of mid -rise, multi -family buildings equipped with a NFPA 13R sprinkler system. 904.13 MODIFIED SECTION. Domestic Cooking in Institutional Occupancies — Establishes requirements for the protection of domestic cooking appliances in care facilities by an automatic fire -extinguishing system. 907.2.10 DELETED SECTION. Group Rd Fire Alarm System — Fire alarm systems are no longer required in Group R-4 occupancies. 910.5 MODIFIED SECTION. Maintenance of Smoke and Heat Removal Equipment — Maintenance and testing frequencies for smoke and heat vents and mechanical smoke removal are now specified in the code. 916 MODIFIED SECTION. Gas Detection Systems — Requirements for gas detection systems are clarified and consolidated in this section. 1006.3 MODIFIED SECTION. Exits on Adjacent Stories — Clarifies egress requirements when the occupants travel to an adjacent story to reach an exit. 1010.1.1 CLARIFICATION. Size of Doors — Requirements for the size of doors is revised to correlate with ICC Al 17.1. 1010.1.4.4 NEW SECTION. Locking Arrangements in Educational Occupancies — Provide guidance to allow enhanced security measures that still meet egress requirements for classrooms. 1010.3 NEW SECTION. Turnstiles — This section allows security turnstiles, or similar barriers, in the means of egress path. 1031.1 MODIFIED SECTION. Inspection and -testing of Emergency Egress Lighting Provides inspection and testing requirements for emergency egress lighting. Chap. 12 NEW SECTION. Energy Systems — This new chapter has been added to the IFC to address all configurations of energy systems which includes emergency power, standby power, stationary battery storage, and other methods of energy generation and storage. 2311.8 MODIFIED SECTION. Repair of Vehicles Fueled by Lighter -than -air Fuels — Updated requirements for repairing vehicles fueled by compressed or liquified gas to address current Technologies and processes. 2810 NEW SECTION. Outdoor Storage of Pallets at Pallet Manufacturing and Recycling Facilities — Provides criteria for outdoor pallet including height limits and separation to property lines. 3106 NEW SECTION. Outdoor Assembly Events — This section adds requirements specific to outdoor public gatherings and was prompted by several fatal events where structural failures have occurred. 3304.5 MODIFIED SECTION. Fire Watch During Construction and Demolition — Criteria for fire watch and clarification to the functions and duties of the fire watch personnel. Chap. 39 NEW SECTION. Processing and Extraction Facilities — This new chapter was added to specifically regulate the process of extracting oils from plant material. 5103 NEW SECTION. Aerosol Cooking Spray Products — Specifies fire protection requirements for aerosol. Other sections include: 5104,2.2, 5104.3.3, 5104.8, 5106.2.2. 5307.1 MODIFIED SECTION. Liquid Carbon Dioxide Systems for Beverage Dispensing — requirements for liquified CO2 in beverage dispensing applications has been correlated with requirements for gas detection systems. 5307.4 NEW SECTION. Carbon Dioxide Enrichment Systems — Enrichment systems with greater than 100 pounds of CO2 are now regulated by the IFC with facilities expanding due to the proliferation of indoor marijuana cultivation. 5707 NEW SECTION. Mobile Fueling Operations — Requirements applicable to on -demand mobile fueling, permits, and the explicit authority given to the fire code official to regulate these operations. Chap. N NEW SECTION. Indoor Trade Shows and Exhibitions — This new chapter provides specific regulations to address the hazards associated with large trade shows and exhibitions. Prepared by: Brian Greer, Fire Marshal, 410 E. Washington Street, Iowa City, IA 52240 ORDINANCE NO. 18 — XXXX AN ORDINANCE AMENDING TITLE 7, CHAPTER 1, FIRE PREVENTION AND PROTECTION, BY ADOPTING THE 2018 EDITION OF THE INTERNATIONAL FIRE CODE TO REGULATE AND GOVERN THE SAFEGUARDING OF LIFE AND PROPERTY FROM FIRE AND EXPLOSION HAZARDS ARISING FROM THE STORAGE, HANDLING AND USE OF HAZARDOUS SUBSTANCES, MATERIALS AND DEVICES, AND FROM CONDITIONS HAZARDOUS TO LIFE OR PROPERTY IN THE OCCUPANCY OF BUILDINGS AND PREMISES IN THE CITY OF IOWA Cd i"PAND PROVIDING FOR THE ISSUANCE OF PERMITS. NOW, THEREFORE, BE IT ORDAINED BY THE Y COUNCIL OF THE CITY OF IOWA CITY, IOWA: SECTION I. AMENDMENT. 1. Section 1, entitled, "Fire Code Adopted," is hereby dei'eted and the following new Section 1 is inserted in lieu thereof: That a certain document, one (1) copy of which is on file in the office of the City Clerk of the City of Iowa City, being marked and designated as the International Fire Code,, 2018 edition, including errata and Appendix Chapters 1 , C, D, E, F, G; H,1, J, K, and N as published by the International Code Council, be and is hereliyadopted as the Fire Code of the City of Iowa City, in the State of Iowa regulating and govei7ning tFie safeguarding of life and property from fire and explosion hazards arising from the storage; handling 8c ,use of hazardous substances, materials and devices, and from Conditions hazardous to life or pperty in thn occupancy of buildings and premises as herein provided, providing for the zsauatce of permits and each, and all of the regulations, provisions,' penalties, conditions atnl terms of said"Vire Code on file in the office of the City Clerk are hereby referred to;, adopted and made a part hereof, as if fully set out in this ordinance, with the additions, insertiuus, deletions and changes, prescribed in the following sections df#lkordirnance. t, Section 2, entitled "Amendments to Fire Code," is deleted in its entirety and the following nev�,Section 2 is inserted in liex them£ That the;fojlowing sections are hereby revised: Section 101.1 Insect: Iowa City, Iowa Section 10211 ML odify by adding a fifth applicability requirement to the end as follows: 5. A. All A-2 Occupancies that existed prior to August 1, 2007 with an occupant load of 100-298 with an ABDL shall comply with Section 903.2.1.2, provided that there is a change in business ownership, defined as the sale, transfer, or assignment of any legal or equitable ownership interest, except that the owner may show to the building official's satisfaction that said change in ownership is one of form and not substance. Section 104.1.1 Add anew section to read as follows: The code official and members of the fire prevention bureau shall have the powers of a peace officer in performing their duties under this Code. Section 104.1.2 Add a new section to read as follows: The Fire Chief may appoint and designate such members of the Fire Department as fire/police investigators upon being certified by the Iowa Law Enforcement Academy. Fire/police investigators shall have the powers of a peace officer in performing their duties under this Code, including full powers of arrest to effectuate their duties of enforcing city ordinances and state statutes. Notwithstanding his/her status as a peace officer, a fire/police investigator shall be subject to the rules and regulations of the Iowa City Fire Department for all purposes and shall perform such functions as the Fire Chief shall assign. Section 104.12 Add a new section to read as follows: The code official is authorized to order an operation or use stopped, or the evacuation of any premises, building, or vehicle or portion thereof which has or is a fire, life safety or health hazard. Section 105.2 Add a sentence to the end of the section to read as follows: Application for an operational permit shall be submitted with all required information not less than 14 days prior to the event requiring a permit. Section 105.4 Add a sentence to the end of the section to read as follows: The fire code official at the official's sole discretion may send plans to a qualified agency for review. The fire code official shall designate the plans review agency. The applicant shall pay all fees associated with the plan review directly to the outside agency. A certificate of occupancy shall not be issued until the review fees have been paid; Section 105.6 Add a sentence to the end of the section to read as follows: The fire code official at their discretion may send plans for operational permits requests to an outside agency for review. The fire code official shall designate the plans review agency. The applicant shall pay all fees associated with the plan review directly to the outside agency. The permit shall not be issued until the review fees have been paid. Section 109. Delete in its entirety and insert in lieu thereof: See Title 17 Chapter 12 of this Code. Section 110.4 Delete the section and replace with: Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the fire code official, or of a permit or certificate used under provisions of this code, shall be guilty of a simple misdemeanor or municipal infraction, as prescribed in Title 1, Chapter 4 of this Code. Each day that a violation continues after due notice has been served shall be deemed a separate offense. Section 112.4 Delete the section and replace with: No person shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition Section 202 Add a new definition to read as follows: CODE OFFICIAL. The Chief Officer of the Fire Department, the Fire Marshal, or the Chief's authorized representative. Section 202 Add a new definition to read as follows: CROWD MANAGEMENT. Crowd management meshes the design features of a facility, the; established operating features of that facility, and an understanding of the occupants' expected' natural behavior in that facility for a specific type of event. Section 202 Add a new definition to read as follows: EMERGENCY COMMUNICATIONS CENTER. The Johnson goutfy Joint Emergency Communications Center. Section 202 Add a sentence to the end of'FIU LAN Iefinition to read as follows: See City Code 9-4-13 for additional rules and regulations Section 307 See also 6-6 of this Code Section 307.1.2 Add anew section to read as follows:'140u�,s of operation. A person shall not maintain any outdoox burning from 11 p.m., to 7 a.m. unless perrnitted and approved by the fire code official, Section 401.9 Add anew section to read as. follows: Building evacuation. Upon activation of the building fire alarm system or upon notification by other means of detecting and reporting unwanted fire; all building occupants , all -promptly evacuate the building. EXCEPTION: When the emergency evacuation plan, as approved by the fire code official, does not requite: the immediate total evacuation of the building. Section 402.1 Add a new definition to read as follows: CROWD MANAGEMENT. Crowd management meshes the design features of a facility, the established operating features of that facility, and an understanding of the occupants' expected natural behavior in that facility for a specific type of event. Section 403.2.5 Add a new section to read as follows: A-2 Occupancy Crowd Managers. Group A-2 occupancies shall be provided with a minimum of one (1) trained crowd manager anytime occupancy reaches 50 or more. Where the occupant load exceeds 250, additional trained crowd managers shall be provided at a ratio of one (1) crowd manager for every 250 occupants. The crowd manager shall annually receive training approved by the fire code official in crowd management techniques. Section 405.2 Add to the end of the section as follows: Fire and evacuation drills in Group E occupancies shall be conducted in accordance with Section 100.31 of the Code of Iowa. Emergency evacuation/ fire drills shall be conducted at least four tines a year. Not less than two drills shall be conducted between July 1 and December 31 each year and not less than two drills shall be conducted between January 1 and June 30 of each year. The Iowa City Fire Department shall conduct one of the two drills during July 1 and December 31 and one of the two drills during January 1 and June 30 of each year. Fire drills in Group R, Division 2, Fraternities and Sororities, shall be conducted once per academic semester. Section 405.2 Table Add footnote e. as follows: Group E occupancies, excluding Preschools and Daycares shall conduct fire and evacuation drills at least four times a year in accordance with Section100.31 of the Code of Iowa. Footnote shall be added to Group E occupancy frequency. Section 503.2.9 Add a new section to read as follows: Thickness. Fire apparatus access roads shall be constructed of Portland cement concreteconforming to the specifications of the Iowa Department of Transportation C-3 or M-3 mixes. The concrete access road shall be a minimum of 7 inches thick over compacted soil. Section 505.1 Delete the section and replace with: New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address identification characters shall contrast: with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall be a minimum of 4 inches high with a minimum stroke width of 0.5 inch. From 100-199 ft from the street the number shall be a minimum of 6 inches high with a minimum stroke of 0.5 inches. From 200-299 ft'from the street the number shall be a minimum of 8 inches high with a minimum stroke of 0.5 inches. For each additional 100 ft from the street, the number shall increase by an additional 2 inches in height. Measurements to determine the minimum number size shall be measured from the approved address location:to the center line of the street for which the premises is addressed. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other.sign or means shall be used to identify the structure. Address identification shall be maintained. Section 506.1 Add a sentence to the end of the section to read as follows: An approved key box shall be installed in an approved location on all new construction. EXCEPTION: Group R-3 and unsecured R-2 occupancies. Section 507.3 Delete the section and replace with: Fire flow. Fire flow requirements for buildings or portions of buildings shall be determined by "Appendix B" of this code. Section 507.5.1 Delete exceptions 1 & 2. Section 507.5.1.1 Delete the section and replace with: Hydrant for fire sprinkler and standpipe systems. A fire hydrant shall be located not more than 100 feet from a fire sprinkler or standpipe system connection on hard surface, easily accessible by fire apparatus and meeting the approval of the Code Official. Section 507.5.7 Add a new section to read as follows: Fire hydrant threads: All new hydrants within the limits of Iowa City installed after January 1, 2020 shall have National Standard Threads (NST) on the two and one-half (2 1/2) inch connections and the four and one- half (4 1/2) inch connection will have a Storz connection. Section 510.1 Delete exception 1. Section 604.9 Delete the section and replace with: Temporary wiring. Temporary wiring for electrical power and lighting installations is allowed for a period not to exceed 90 days for holiday decorative lighting, carnivals and similar purposes. Temporary wiring methods shall meet the applicable provisions of the Iowa City Electrical CA6, EXCEPTION: Temporary wiring for electrical powe�`and lighting installations is allowed during periods of construction, remodeling, repair or qnt jil§' of buildings, structures, equipment or similar activities. Temporary wiring m N ods shall xrieet the applicable provisions of the Iowa City Electrical Code. Section 604.10 Delete the section and r4lace with: Portable electn43 space heaters. Portable electric space heaters shall comply with Sections 6".1 through 1.10.6. Section 604.10.6 Add a new section to read as f Ildws: Fully enclosed. Portable, electric space heaters shall be fully enclosed apace.heaters that by d'esign have no external surfaces that reach temperatures capable of igniting materials placed against the surface. Section 606.7 Adel a sentence to the end of the section to rea' d'as follows: The Fire Code Official may requirean'approved elevator key box in an approved location to secure required elevator keys. Section 607.4 Delete the last seatence and replace with: Movement of new and existing cooking appliances with caster(*) under'a Ty q 1. hood shall be limited by an approved floor mounted restraining device and flexible gas connector installed in accordance with the connector and appliance manufacturer's instru'ei1'ons. Section 9014.5 Add a new section to read as follows: Maintenance. The interior finish of buildings shall be maintained in accordance with the conditions of original approval. Any change to the interior finish that is'regulated by the provisions of this code or the building code shall be made in accordancewtl all applicable requirements. Section 806.1 Add a sentence to the end of the section to read as follows: Natural or resin -bearing cut trees and natural decorative vegetation used in buildings open to the general public shall be properly treated with an approved flame retardant. Section 807.5.2.1 Delete exception 2. Section 807.5.5.1 Delete exception 2. Section 901.2 (a) Add a new section to read as follows: Water based fire protection systems. Working plans submitted to the fire department for water based fire protection systems shall be stamped and approved by a qualified person to be in compliance with applicable NFPA standards and the Iowa City Fire Code. Any changes to the working plans shall be approved by a qualified person. A qualified person shall have a minimum National Institute for Certification in Engineering Technologies [NICET] Level III certification for Automatic Sprinkler System Layout OR be a licensed engineer with experience in life safety system design. Other qualifications may be approved by the code official. Section 901.2 (b) Add a new section to read as follows: Fire alarm systems. Working plans submitted to the fire department by a qualified person for fire alarm systems shall be stamped and approved by a qualified person to be in compliance with applicable NFPA standards and the Iowa City Fire Code. Any changes to the working plans shall be approved by a qualified person. A qualified person shall have a minimum National Institute for Certification in Engineering Technologies [NICET] Level III certification for Fire Alarm Systems OR be a licensed engineer with experience in life safety system design. Other qualifications may be approved by the code official. Section 901.6.3.2 Add a new section to read as follows: Inspection record submission. Contractors who perform installation, inspection, testing, and/or maintenance services on fire and life safety systems are required to electronically submit all installation and compliant & non- compliant inspection reports to the Fire Department via a method approved by the Fire Code Official within 30 calendar days of the installation/inspection date. Reports submitted after 30 calendar days may incur late fees. Section 901.7 Add a section, to the end of the section to read as follows: A person assigned to fire watch must walk through the building at least once every 30 minutes checking for fire or smoke. A fire watch.must be continued until the fire alarm system and/ or fire protection system has been restored to normal operating condition or the building has been evacuated. A competent adult familiar with the building must conduct the fire watch. If a fire is discovered, 911 shall be called immediately and the building evacuated. Section 903.2.1.2 Delete Section 903.2.1.2 and insert in lieu thereof the following: Section 903.2.1.2 A. New Group A-2 Occupancies. An automatic sprinkler system shall be provided for fire areas containing Group A-2 occupancies and intervening floors of the building where one of the following conditions exist: 1) The fire area exceeds 5,000 square feet; 2) The fire area has an occupant load of 100 or more; or 3) The fire area is located on a floor other than the level of exit discharge. B. Existing Group A-2 Occupancies that existed prior to August 1, 2007: An automatic sprinkler system shall be provided throughout the A-2 occupancy with an occupant load of 100 or more that have an ABDL and there is a change in business ownership, defined as the sale, transfer, or assignment of any legal or equitable ownership interest, except that the owner may show to the building official's satisfaction that said change in ownership is one of form and not substance. Section 903.2.1.8 Add a new Section to read as follows: An automatic sprinkler system shall be provided throughout buildings and portions thereof used as new Group B occupancies with an ABDL or existing group B occupancy with a new (not a renewal) ABDL located on a floor other than the level of exit discharge. The automatic sprinkler system shall be provided throughout the floor area where the new Group B occupancy with an ABDL or where the group B occupancy with a new ABDL is located and in all floors between the Group B occupancy and the level of exit discharge. Section 903.2.2 Delete the section and replace with: Ambulatory care facilities. An automatic sprinkler system shall be installed throughout all fitO;,areas containing an ambulatory care facility and all floors between the ambulatory care f4piltfy and the level of exit discharge serving such a facility. Section 903.3.5.3 Add a new section to read as follows Watd�t­_.supply safety margin. Automatic sprinkler systems shall be designed with a minimum of 10U15r. 5 psi safety margin (whichever is greater) above static pressure in the. fire protection system hydraulic calculations. Section 903.4.2 Delete the section and replace with: Alarms. An approvad.weatherproof hom/strobe device shall be mounted directly above the fire department connection between seven (7) and ten (10) feet in height above -grade. The water -flow alarm device shall be activated by water flow equivalent to the flow of a .single:sprinkler of the smallest orifice size installed in the system. Approved and supervised audible visual Pgtification appliances shall be installed on each level of the interior of the building as required by the fire code official and NFPA 72. Section 903.7 Add anew section to reafl as follows Zones. Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13 or NFPA 13R and shall provide a sprinkler control,vglve and waterflow device for each,normally occupied floor. The location of sprinkler,confrol val"+es must be approved by the fire ode official. Sed on 905.1.1 Add &new section to read as follows: delete all references to Class 11 standpipe systems and replace with Class III standpipe systems. Section 905 4ARequirement -1; Delete the section and replace with: In every required interior exit stairway, a hose' connection-�lall be provided for each story above and below grade plane. Hose connections shall belocat9 at intermediate landing between stories, unless otherwise approved by the fire code official. Section 906.1 Delete exceptions 1 & 2 without substitution. Section 906.3 Add a sentence to the end of the section to read as follows: The minimum rating of any required portable fire extinguisher for Class A, Class B, or Class C hazard shall be 2-A, 10-B C. Section 907.1.4 Add a new section to read as follows: Fire alarm control panels and Fire alarm annunciator panels. Installation of fire alarm control panels and fire alarm annunciator panels shall be installed in accordance with section 907.1.4.1 through 907.1.4.5. Section 907.1.4.1 Add a new section to read as follows: Fire Alarm Panel Height: Installation of fire alarm panels shall not exceed 6 feet in height measured from the floor to the top of the panel. Exception: Panel height may be altered by the code official. Section 907.1.4.2 Add a new section to read as follows: Number of Fire Alarm Control Panels in Buildings: Only one listed fire alarm control panel shall be allowed per building and shall lock in the alarm until the system is reset and shall not be canceled by the operation of an audible — alarm silencing switch. This control panel shall only receive alarm signals from fire protection equipment. Section 907.1.4.3 Add a new section to read as follows: Combination Fire/Security Alarm System Panels. A listed combination fire/security alarm system panel that meets all the requirements of this code and amendments maybe permitted by approval of the fire code official. The fire/security panel shall be capable of providing a signal that can differentiate between the fire and security alarm. Section 907.1.4.4 Add a new section to read as follows: Password/PIN Protection Prohibited: Fire alarm control panels and/or fire alarm annunciator panels that require a password/PIN to silence an, alann/supervisory/trouble signal and/or to reset an alarm/supervisory/trouble signal shall be prohibited. Section 907.1.4.5 Add a new section to read as follows: Fire Alarm Annunciator Panels: The fire code official can require the addition of fire alarm annunciator panels based on the size of building and access to the bu.ilding.These panels shall meet the requirements of Sections 907.1.4 and 907.2. Section 907.2 Delete the section and replace with: Where required —new buildings and structures. An approved and addressable manual, automatic, or manual and automatic fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.23 and provide occupant notification in accordance with 907.5, unless other requirements are provided by another section of this code or the fire code official. A minimum of one manual fire alarm box shall be provided in an approved location to initiate a fire alarm signal for fire alarm systems employing automatic fire detectors or water -flow detection devices. Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, a single fire alarm box shall be installed. EXCEPTION: 1. The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service. 2. The manual fire alarm box is required for Group R-2 occupancies to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. The manual fire alarm box shall not be located in an area that is accessible to the public. 3. Multi -tenant buildings required to have a manual/automatic fire alarm system shall install a minimum of one manual pull station per tenant space. Section 907.2.1 Delete the exception in Section 907.2.1 in its entirety and insert in lieu thereof the following exceptions: EXCEPTION: 1) Except for Group A-2 occupancies with occupant loads of 200 or more, manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow. 2) Group A-2. An automaticlmanual fire alarm system shall be installed in Group A-2 occupancies with occupant loads of 200 or more. Activation of the fire alarm shall additionally cause: a. Illumination of the protected premises to not less than l0 foot-candles over the area of the room at a height of 30 inches above the floor; and b. All conflicting or confusing sounds and visual distraction to automatically stop. Section 907.2.3 Modify by adding a sentence to the end of the first paragraph as follows: New and existing educational occupancies shall have s monitored fire alarm system. Section 907.2.3 Modify by adding a 5th exception, as follows: 5. Day care occupancies classified as Group E.Occupancyshall not require a monitored fire alarm system unless required elsewhere in the code; Section 907.2.9.1 i9eTst exception 2 without substitution Section 907 2 .10.2 Modifj«ay, adding a4burth location requirement as follows: 4) Supervised smoke alarms shalllie: installed in all common corridors and at the top and bottom of all stairway enclosures in trroupa R,2 R; 4 and I} , occupancies. In corridors, detectors shall be located *Ohin i�Ftei n (15) fed ' -'of the erid of the'corridor and in such a way that one detector is located for each thirty (36) feet of' 'corridor length,or spaced as allowed by the code. Section 907.2.12.2 Delete the section without substitution. Section 9074.2 Add a sentence to the end of the section to read as follows: Where in the opinion of the code official manual fire alarm boxes may be used to cause false fire alarms, the code official is authorized to modify the requirements for manual fire alarm boxes. Section 907.6.4 Modify by deleting the exception and inserting in lieu thereof. Exception: Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13 and shall provide a sprinkler control valve and waterflow device for each normally occupied floor. Section 907.6.4.3 Add a section to read as follows: Zone and address location labeling. Fire alarm and/or annunciator panels shall have all zones and address points plainly and permanently labeled as to their location on the outside of the panel or on an easily readable map of the building, if no display is present. Section 907.6.6 Add to the end of the section as follows: Each address point identification shall have an alpha/numeric descriptor location. Alpha/numeric descriptor locations are required to be reported to the Emergency Communications Center upon activation of alarm conditions as specified by the fire code official. Supervisory alarm conditions are required to be reported to the fire code official by an approved manner. Section 907.11 Add a new section to read as follows: Approved hold open devices. When installed in buildings that have a fire alarm system and/or sprinkler system, all approved hold open devices shall release upon activation of a fire alarm and/or sprinkler water -flow activation. Section 912.4.1 Delete the section and replace with: Locking fire department connection caps. Locking fire department connection caps approved by the fire department are required for all new construction that have a water -based fire protection system and existing structures that have a water -based fire protection system shall be required immediately after conducting the five-year obstruction and maintenance testing, or if one or more of the fire department caps are missing. Section 912.8 Add a section to read as follows: Size. Minimum fire department connection size shall be 2 ''/2" National Standard Thread, Section 1029.2 Add the following exception: EXCEPTION: The main entrance/exit of A-2 occupancies shall be of a width that accommodates not less than two-thirds of the total occupant load. Section 1030.1 Modify by deleting exceptions 1 and 3. Section 5003.5 Add a sentence to the end of the section to read as follows: Signs shall also comply with the requirements of the Iowa Right to Know law. Section 5704.29 Add a sentence to the end of the section to read as follows: For aboveground storage tanks'of 276 gallons capacity or more, the minimum distance between such aboveground tanks and any Residential Zone boundary must be at least 100 feet. If the aboveground tank is located in an approved vault, the minimum separation distance from a Residential Zone boundary may be reduced to no less than 50 feet. Section 5704.2 11.1 Add #4 to the end of the section to read as follows: 4) A minimum distance of ten (10) feet shall be maintained between underground tanks and any Residential Zone boundary. Section 5704.2.13.2.4 Add a section to read as follows: Existing above -ground tank hazards. Existing above -ground tank installations, even if previously approved, that are determined to constitute a hazard by the fire code official, shall not be continued in service. Unsafe tanks shall be removed as required by the fire code official and in accordance with this code. 3. Section 3. That the geographic limits referred to in certain sections of the 2018 International Fire Code are hereby established as follows: Section 5704.2.9.6.1. The storage of Class I and Class II liquids in above -ground tanks outside of buildings is prohibited in the entire City of Iowa City, Iowa Exception: Zones 11 &2, CI 1 and/or as approved by the Fire Chief Section 5706.2.4.4. The storage of Class I and Class II liquids in above -ground tanks is prohibited in the entire City of Iowa City, Iowa. Exception: Zones 11 &2, Cl 1 and/or as approved by the Fire Chief. Section 6104.2. The storage of liquefied petroleum gas is prohibited in the entire City of Iowa City, Iowa. Exception: Zones 11 &2, CI 1 and/or as approved by the Fire Chief. SECTION II. REPEALER. All ordinances and. ;parts of ordinances in conflict with the provisions of this Ordinance are hereby repealed. SECTION III. SEVERABILITY. If any section, prbvi,. sion or part of the Ordinance shall be adjudged to be invalid or unconstitutional, such adjudicatit shall not affect the validity of the Ordinance as a whole or any,section, provision or'partthereof n691udged invalid or unconstitutional. `:: SECTION IV'. EMPECTIVE DATE. Thip Ordinance shall be in full force and effect XXX3XX 1, 2019, after finial passage,- approval and publication, as provided by law. Passed and approved this day of 2019. MAYOR ATTEST: CITY CLERK Approved by: City Attorney's Office